2020年7月27日星期一

bus bar bender machinebusbar punching machine

Clearance and creepage distance

 

5.2 The electrical clearance and creepage distance between the live parts in the device and the metal parts to the ground should meet the requirements of 5.2 and 5.3.

bending machine for busbar

5.3 The electrical clearances and creepage distances between all horizontal busbars, vertical busbars, branch lines and live parts of main circuit connectors and between grounded metal parts should be not less than 20mm when the rated insulation voltage is 380V and 660V (this article The regulations apply to low-voltage drawer-type switchgear. For low-voltage fixed-type switchgear, refer to Table 8.   

                               Tabl

 Predetermined insulation voltageUi      busbar trunking machine.0000pt;">

            Electrical clearance mm

          Creepage distance mm                       

    63AAnd below           

    more than the63A       

   63AAnd below       

    more than the63A    

    Ui≤60

       3

       5

       3

       5

  60<Ui≤300

       5

       6

       6

       8

 300<Ui≤660

       8

       10

      10

       12

hydraulic cnc copper busbar cutting punching machine

Note: The thermal stress and electrical stress should be considered when selecting the clearance and creepage distance of the main busbar and the high-current busbar

 

5.4.1 The distance between the inlet and outlet terminals of the universal circuit breaker is less than the above provisions, then the clearance and creepage distance of the branch lines on the connection terminals are allowed to be equal to the spacing between the terminals, but not less than those specified in Table 8.

5.4.2 If non-insulated metals (such as screws, spring pads, gaskets, etc.) are added between bare live parts of different polarities or between bare live parts and grounded metal, this is considered to be a reduction of the gap.

5.4.3 When a part of the busbar or busbar connection fails to meet the requirements of 5.2, the method of wrapping insulating tape is allowed, but it shall not be less than the requirements of Table 8.

5.4.4 See Table 9 for the electrical clearance and creepage distance of the high-voltage cabinet

      Table九

Rated voltageKV

Electrical clearancemm

Creepage distancemm

3

100

140

6

125

160

10

125*

216

35

300

729

bending press machine

Electrical clearance for products that have been shaped by national unified design may be less than 125mm, but not less than 100mm

没有评论:

发表评论