Busbar arrangement and color marking
4.2 Provisions for selecting wire colors according to the circuit (GB2681) (see Table 6)
4.3 Table 6
Serial number |
Circuit |
Busbar color code |
1 |
Phase A of an AC three-phase circuit Phase B Phase C Neutral or neutral Ground wire for safety |
Yellow Green Red light blue Yellow and green |
2 |
Positive pole of DC circuit negative electrode Ground intermediate |
hydraulic busbar bending cutting punching
machine.0000pt solid windowtext;">
Brown Blue light blue |
Note: A. The surface of the low-voltage cabinet busbar is tinned, and the color code of the color specified in the table is pasted on the maintenance surface busbar of the cabinet body.
B. The surface of the busbar of the high-voltage cabinet is tinned, and then the color code of the color specified in the table is pasted on the busbar of the maintenance surface of the cabinet body.
4.5 The arrangement of busbars shall meet the requirements of Table VII Table七
Differ |
Vertical arrangement |
Horizontal arrangement |
Downline |
A |
on |
Rear |
left |
B |
in |
in |
in |
C |
under |
before |
right |
Neutral |
Bottom |
First |
Most right |
positive electrode |
Up |
Rear |
left |
negative electrode |
under |
before |
right |
Description: 1. The orientation is based on the front view of the screen.
2. Under special circumstances, for example, the arrangement of low-voltage cabinets will cause difficulties in bus bar configuration, and it is allowed not to comply with Table 7.
3. When the high-voltage cabinet 35KV cabinet is used for communication, the down wires are arranged vertically, and the regulations in Table 7 are not followed.
没有评论: